Electronic water analyzer eSELECT B3 pH / Rx / CL
eSELECT B3 is a high-precision electronic liquid analyzer for measuring electrochemical parameters: pH, RedOx (ORP), free (total) organic or inorganic chlorine to choose from.
The electronic controller eSELECT B3 is equipped with a color LCD display with backlight and includes a Russified menu, made in a plastic case for wall mounting.
The eSELECT B3 Liquid Analyzer contains galvanically isolated electronic components that provide a high level of immunity to electromagnetic interference.
Name |
vendor code |
Liquid analyzer eSELECT B3, 90-260V |
CXB5010101 |
Liquid analyzer eSELECT B3, 12V DC - 24V DC /AC |
CXB5010111 |
SPECIFICATIONS
- Three measuring parameters to choose from: pH or Rx or free /total chlorine CL or measurement in PPM mode.
- Continuous dosing time alarm.
- Alarm signaling for concentration limits of MIN /MAX levels.
- Menu type selection: Standard /Expert.
- Russified menu.
- Start delay, measurement delay.
- Password protection of the settings made.
- The controller has a dosing control mode: constant ON /OFF and PROP. proportional.
- Two independent ON / OFF outputs (non-contact relay) for each measured parameter.
- Two independent 4-20 mA outputs for each SETPOINT.
- The liquid analyzer supports the connection of a flow sensor, a reagent level sensor, and a PT100 temperature sensor (sensors not included).
- Automatic temperature compensation (when connecting a PT100 sensor).
- The controller has a clock and a timer for daily or weekly programming of operating modes.
- Power supply voltage in standard version: 90-260 V AC 50/60 Hz; on request: 12-24 V DC; 24 VAC.
- Power consumption: 15W (1A peak current).
- Operating temperature range: 0-40 ° C.
- Dust and moisture protection class: IP65.
- PH measurement range: 0-14 (resolution 0.01pH).
- RedOx measurement range (ORP): –1000 ... + 1400 mV (resolution 1mV).
- Chlorine measurement range (free or residual): 0-2 mg /l; 0-20 mg /l; 0-200 mg /l; 0-2000 mg /l (resolution 0.001 /0.01 /0.1 /1 mg /l).
- Measurement range in PPM mode: 0-2 PPM; 0-20 PPM; 0-200 PPM; 0-2000 PPM (resolution 0.001 /0.01 /0.1 /1 PPM).
- Measured temperature range: 0-100 ° C (resolution 0.1 ° C).
The eSELECT B3 Liquid Analyzer is equipped with the following outputs:
- Relay output ON /OFF (non-contact relay NO /NC) for controlling metering pumps or other actuators operating in ON /OFF mode (max.current 16A with resistive load; 3A with inductive load).
- Two independent ON /OFF relay outputs per measurement channel.
- Current output (analog): 4-20 mA (dynamic 0..500 Ω).
Two independent current outputs 4-20 mA per measurement channel.
- TTL output: 0-999 pulses /min. Two independent TTL outputs per measurement channel.
- Alarm relay output ALARM ON /OFF (non-contact relay NO /NC), alarm on time of continuous dosing and on limit concentrations of MIN /MAX levels
(max. current 5A with resistive load; 0.7A with inductive load).
- AUX ON /OFF relay output for timer control of actuators (scheduled operation)
(max. current 5A with resistive load; 0.7A with inductive load).
- RS232 output (RS232 serial port) for connecting a PC or supervisor.
The eSELECT B3 Liquid Analyzer is equipped with the following inputs:
- BNC input for connecting a signal from pH or RedOx or Chlorine sensors.
- Input (plug type "Hirschmann") for connecting the power supply to the SONDA CL chlorine sensor.
- Flow sensor input.
- Input for connecting a PT100 temperature sensor.
- Input for the reagent level sensor.
- The controller has two independent inputs for a reagent level sensor per measurement channel.
This category does not contain any products.